Yahoo India Web Search

Search results

  1. Nov 4, 2012 · Steam pipes can be sized with the table and diagram below - pressure in bar, velocity in m/s and capacity in kg/h. Sizing Steam Pipes - Imperial units (lb/h) Download Sizing Steam Pipes Chart in pdf-format. Steam velocities of 25 m/s are in general sufficient for most saturated steam applications. Sizing Steam Pipes - Imperial units (lb/h)

  2. Online calculator to quickly determine Steam Flow Rate through Piping. Includes 53 different calculations. Equations displayed for easy reference.

  3. Nov 4, 2012 · in general - 80 ft/sec is a recommended steam velocity. Sizing Steam Pipes - in SI units (kg/h) Steam pressure vs. saturation temperature. Download Sizing Steam Pipe Lines Chart in pdf format. Example - Sizing Steam Pipe Lines. A 4 inch sch. 80 steel pipe with 100 psi steam pressure has a capacity of 5923 lb/h with steam velocity 80 ft/s.

  4. Steam Sizing Chart. Determining the Value Cv. Cv calculation is an interactive process requiring knowledge of valve dynamics, piping geometry factors, and outlet velocities. In practice, this sizing chart is based on emperical values and will cater for most applica- This chart is for example only. A complete chart for sizing is overleaf. tions.

  5. PROPERTIES OF STEAM. Example: 6800 lbs per hour of steam flow in a 2 1 / 2 inch pipe at 100 psig pressure. What is the pressure (psi) drop per 100 ft length of pipe and the flow velocity? Answer: psi/100' = 11 velocity = 32,000 fpm. Figure - 17 Steam Flow Rates at Various Pressures and Velocities for Schedule 40 Pipe Source: ASHRAE.

  6. Jul 5, 2024 · Proceed by calculating the required Cv from given flow data, having prior determined whether the flow is critical or sub-critical. The following equations have been adapted from the ISA S75.01 standard to allow for practical everyday use without significant sacrifice in accuracy. For steam service Subcritical flow Critical flow When ∆P is ...

  7. Pipe sizing is a key aspect of steam system design. Learn more about standards, schedules, materials and sizing for many saturated and superheated steam duties.

  8. STEAM AND CONDENSATE PIPING SIZES. Please use with care, and understanding of Steam Piping design NOTE: This document is being supplied for reference only. RULE OF THUMB TO ACHIEVE: 6,000 to 12,000 fpm ( Feet per Minute ) Which is also: 100 Feet / Second to 200 Feet per Second.

  9. Saturated Steam Sizing Chart How to use the chart Example 1: How to find K v value for a critical flow application. Steam demand of heat exchanger = 800 kg/h Steam pressure upstream of valve = 8 bar g = 9 bar a Steam pressure required in exchanger = 3 bar g = 4 bar a Using the selection chart: Draw a horizontal line from 800 kg/h

  10. Basic Steam Pipe Sizing Charts. Re-Evaporation Chart. Figure 22 - Velocity Multiplier Chart Example of Use of Basic and Velocity Multiplier Charts. Given: Weight – Flow Rate = 6700 lb per hr. Initial Steam Pressure = 100 psig. Pressure Drop = 11 psi per 100 ft. Find: Size of Schedule 40 pipe required. Velocity of steam in pipe.